+86 021 67109909     +86 18017809222
All Categories

Home > Products > Embedded Pole

  • Embedded Pole Cylinder 405kV EEP-4052500-315 EEP-4052000-315
  • Embedded Pole Cylinder 405kV EEP-4052500-315 EEP-4052000-315

Embedded Pole Cylinder 405kV EEP-4052500-315 EEP-4052000-315

Description:

Embedded pole cylinder with epoxy resin,is made by casting vacuum interrupters,main circuit conduct and mounting parts with epoxy into an integral part. The vacuum interrupters, however,should be enveloped well with a slight fold of silicon rubber jacket before that process.

  • Product Description

Model No: EEP-40.5/2500-31.5 EEP-40.5/2000-31.5

Embedded pole cylinder with epoxy resin,is made by casting vacuum interrupters,main circuit conduct and mounting parts with epoxy into an integral part. The vacuum interrupters, however,should be enveloped well with a slight fold of silicon rubber jacket before that process.

Parameters of Embedded pole cylinder

MAIN TECHNICAL SPECIFICATION UNIT SPECIFICATION
2500 2000
Rated voltage kV 40.5
Rated current A 2500 2000
Rated frequency Hz 50/60
Short-duration1min) power frequency withstand voltage  kV 95
Lightning impulse withstand voltage kV 185
Rated short-circuit breaking current kA 31.5
Rated peak withstand current kA 80
Rated short-circuit making current kA 80
Rated short-time withstand current kA 31.5
Rated duration of short-circuit S 4
Rated breaking current of single capacitor bank A 400
Rated breaking current of back to back capacitor bank A 400
Rated operating sequence o-0.3S-co180S-co
Breaking operations of rated short circuit breaking current Time 20
Mechanical endurance Time 10000
Contact self-close force N 120±50 
Force required to hold contacts open at full stroke N 240±50 
Circuit resistance at lower limit of rated contact force ≤ 30 
Contact limit erosion mm 3
Gas pressure inside vacuum interrupter Pa ≤ 1X10-3 
Partial discharge Pc ≤ 
Weight of moving parts Kg
Weight of vacuum interrupter embedded poles Kg

 

Mechanical data required for the matched vacuum switchgear

MAIN TECHNICAL SPECIFICATION UNIT SPECIFICATION
2500 2000
Clearance between open contacts mm 18±
Average opening speed m/s 1.55±0.15 
Average closing speed m/s 0.7±0.2 
Rated contact pressure N 3200±200 
Contact bouncing duration at closing operation ms ≤ 
Out of simultaneity of contact closing and opening ms ≤ 
Bouncing back amplitude of opening contact mm ≤ 

Information for Embedded pole cylinder

From the development of insulations on breakers,it can be divided into three generations:air, composite and solid insulation and so-called solid insulation means Embedded pole cylinder,which might represent the great advancement of insulation on vacuum breakers.Since the epoxy can be used to replace the insulating and mechanical supports,the breakers therefore become compact and simple and are able to service under humid and dusty conditions.When the external insulations of miniature chambers in air condition fail to fulfill the requests of specifications,Embedded pole cylinder are therefore introduced and now become one of the most applicable ways in the field of medium voltage breakers either at home or abroad.

Embedded pole cylinder 24kV EEP-40.5/2500-31.5 EEP-40.5/2000-31.5

drawing Embedded pole cylinder 40.5kV EEP-40.5/2500-31.5 EEP-40.5/2000-31.5

 

About us
We are specialty on Embedded pole cylinder of medium voltage and high voltage components, such as 12KV, 24 KV, 36KV and 40.5KV switchgear bushing, contactor box, insulators, transducers. 630A, 1250A, 2500A, 3150A and 4000A contactor box, club contact, fix contact, arm contact and jaw contact. 630A and 1250A VS1 circuit breaker. 630A and 1250A ZN85-40.5 circuit breaker. 12KV and 24KV earth switch. KYN28A-12 and KYN61 high voltage switchgear components.